FP-924 soiling and cleaning audit

Plant FP-924 (2,952 kWp, 35 inverters, 25 blocks). Data: Solar Link daily inverter energy 3-Jul-2025 to 22-Nov-2026, 5-min power 22-Oct to 22-Nov-2026, SMP3 pyranometer, ERA5 weather, CAMS PM10. Economics year: 2025-11-23 to 2026-11-22 (measured meter energy 4,210,888 kWh).

Verdict. The current ₹3.65 lakh/yr net figure is too high: it sits at the upper bound. The 0.258 %/day rate comes from a step detector that the data do not support (output does not decay again after detected cleanings: -0.003 %/day vs −0.215 %/day expected). Best defensible estimate: ≈₹0.91 L/yr net (range ₹0 to ₹5.54 L), cleaning about every 31 dry days.

Answers at a glance

QuestionShort answerVerdict
1. Existing calculationsEquations are mostly right; the inputs are not. The 0.258 %/day rate and the 'observed' cleaning interval come from noise-driven step detection.Overstated
2. Are dust losses underestimated?No. Sensor soiling and the campus-relative method hide some plant-wide dust, but rain tests cap it near 2.3 % after 21–42 dry days (up to 11 % in the haze-inflated bound).Not underestimated
3. ScenariosA ₹0 · B ₹0.91 L · C ₹5.54 L net per year.B most credible
4. Optimal interval / break-evenB: clean every ~31 dry days (4 rounds/yr); pays only below ₹10.7/module. Block-specific schedule adds ≈ ₹0.Whole-plant schedule
5. Biggest driverDust rate (swing ₹5.17 L), then cleaning cost and the rain threshold. Monte Carlo P5–P95: ₹0.00 L to ₹3.70 L.Rate must be measured
6. Physical validityCapacity OK except 12 logger-dump days; γ = −0.29 %/°C correct; portal 'POA' is really GHI; 27 'cleanings' are fault recoveries.Fix data flags
7. RecommendationPresent B as the headline, A–C as the range, and a 60-day measurement plan to validate C.Honest range

1. Audit of the existing FP-924 calculations

Each listed item was recomputed from the raw exports where the data allowed.

ItemFindingTagVerdict
Generation / inverter dataLast 365 d: 4,210,888 kWh meter (1426.4 kWh/kWp); meter ÷ inverters = 1.0064. 12 inverter-days exceed 7.2 kWh/kWp (max 9.99) = logger catch-up dumps, not real.MeasuredFlag & drop dumps (not done in Solpop)
DC / AC capacity2952.2 kWp / 2479.89 kW (ratio 1.19); ≈4,840 modules (portal field blank).Measured / calculatedOK
POA irradiance & weatherPortal 'POA' tracks GHI (horizontal sensor). Tilt/azimuth not recorded (assumed 20°/10°/7°, south). Sensor ratio to ERA5 jumps 0.758 → 0.971 on 11-Nov-2026 (sensor dirt or rescale).MeasuredSensor itself soils; masks dust in PI
Expected energyIsotropic POA × NOCT × 0.96 is acceptable. Clipping ignored: 16 inverters hit AC limit; 0.33 % of Oct–Nov energy at limit (worst 3.6 %).CalculatedMinor
Module temperatureγ = −0.29 %/°C and NOCT 43 °C match Trina datasheet. Module-temperature sensor reads NaN, so NOCT is unvalidated.AssumedOK (small effect)
Performance IndexClear-day plant PI swings 0.78 (winter) → 0.96 (summer). 43 mm of rain restored only 2.3 %, so this swing is shading/sun-angle/fog, not dust.CalculatedDo not call it soiling
Soiling RatioSR = PI ÷ post-rain (≥8 mm) PI. Reasonable, but the reference inherits sensor dirt and partial rain cleaning.CalculatedAcceptable as relative
Daily soiling rate0.258 %/day = median step ÷ days. After detected cleanings the block output stays flat (-0.003 %/day, 95 % CI -0.021 to +0.017).InferredNot supported
Cleaning-event identification169 events confirmed; threshold 3.5 % ≈ 1.5× daily noise (2.3 %). Pure noise alone yields 35 events; lowering threshold to 2 % gives 551. 27 events follow a fault 'drop'.InferredNot a cleaning log
Interval optimisationT* = √(2C/(pEr)) is correct for linear dust, but E was a November forecast (≈9,200 kWh/d) not the annual mean (11,537 kWh/d), and the 'observed' interval (17–118 d by block) comes from the same unreliable events.CalculatedFormula OK, inputs not
Tariff & cleaning cost₹7.75/kWh and ₹6/module are assumptions (no bill or crew cost data).AssumedTest in sensitivity

Red flags verified

ClaimRecomputedStatus
Detected crew cleanings169 (2025-11-12 – 2026-11-21)Confirmed
Min / median step3.5 % / 5.9 %Confirmed
Step vs days-since-reset, r0.035 (p = 0.71)Confirmed
LOO error: constant vs linear1.83 vs 3.89 ptsConfirmed
'Drop' events52; 27 cleanings come ≤30 d after a dropFaults mixed with dust

Artefact or plateau? Neither explanation in the brief fits. A synthetic test (hypothetical series, real noise) shows the detector gives r ≈ 0.09 even when dust is truly linear, and over-states a true 0.258 %/day as 0.48 %/day. The low correlation is a detection artefact, but it pushes the rate up, not down.

Block output vs campus around the 169 detected cleanings. Linear dust at 0.258 %/day would follow the dashed line.
Block output vs campus around the 169 detected cleanings. Linear dust at 0.258 %/day would follow the dashed line.

2. Are dust losses underestimated?

Short answer: no. Two mechanisms do hide dust, but the rain experiments bound the hidden part.

PossibilityAnswerEvidence
Seasonal variationPartlyPM10 peaks Apr–Jun and Oct–Nov; a season-specific rate model does not beat the campus model out of sample (3.88 vs 3.89 pts).
Block-to-block differencesNoBlock-vs-campus decay after cleanings is ≤ 0.02 %/day; block-specific rate model is worse (5.30 pts). Block offsets (H Block, TSLAS, Carport) are shading.
Particulate / local conditionsPartlyCAMS dust is high in Oct–Nov, but haze lowers sunlight, not module transmittance; the dust-flux model lost in Solpop's own LOO.
Long dry periodsYes (handled)Oct–Jan has ~100 dry days; this is where cleaning pays. The day-by-day simulation uses the real rain calendar.
Non-uniform accumulationUnknownBottom-edge dust on 7–10° carport/shed roofs could add mismatch loss; needs string-current or IV data.
Dry vs wet (cemented) soilingNo evidence43 mm of rain after the foggy winter restored only 2.3 % (pyranometer) – no large cemented layer.
Single campus-wide rateNoBlock differences are below detection; one rate is adequate.
Clean-reference effectYes, smallA dirty pyranometer/post-rain reference hides plant-wide dust. Bounded by ERA5: up to 11 % (Jan) / 9 % (Mar), but ~8 pts of that is sky clearing/sensor wash.
Rain after a dry spell cleans every module at once. Pyranometer and ERA5 references bracket the true jump.
Rain after a dry spell cleans every module at once. Pyranometer and ERA5 references bracket the true jump.
Rain daymmDry days beforeJump vs pyranometerJump vs ERA5Sky/sensor change
2026-01-2343.521+2.3 %+11.1 %+7.6 %
2026-03-166.542+2.2 %+9.0 %+7.1 %
2026-04-293.420-1.0 %-1.0 %+0.5 %
2026-05-3021.417-0.1 %+4.0 %+4.0 %

Other losses that cleaning cannot recover: inverter/logger downtime (2.1 % of inverter-days, ≈90,267 kWh in Feb–Nov 2026 – more than scenario B recovers) and winter shading/sun-angle loss.

Left: seasonal PI shape is symmetric about mid-summer (geometry, not dust). Right: H Block and TSLAS swing with the seasons (shading).
Left: seasonal PI shape is symmetric about mid-summer (geometry, not dust). Right: H Block and TSLAS swing with the seasons (shading).

3. Scenarios A / B / C

A = only what the pyranometer rain test proves; B = most likely; C = the existing model's rate, with no saturation and 100 % cleaning recovery.

Scen.Daily soiling rateAnnual dust loss, rain onlyRecoverable by cleaningIntervalCleanings/yrGross valueCleaning costNet savingsRate tag
A0.050 %/d (saturating 3 %)27,936 kWh (0.66 %)0 kWhno routine cleaning0₹0₹0₹0I/As
B0.100 %/d72,391 kWh (1.72 %)26,732 kWh31 d4₹2,07,171₹1,16,160₹91,011I/As
C0.258 %/d188,655 kWh (4.48 %)116,417 kWh16 d12₹9,02,231₹3,48,480₹5,53,751H
InputA conservativeB realisticC upper bound
Rate basis2.2 % ÷ 42 d (Mar rain, pyranometer)2.3 % ÷ 21 d (Jan rain, pyranometer)Existing 0.258 %/d; ≈ ERA5 bound of Mar rain (9 % ÷ 42 d)
Share removed by a cleaning90 % (As)95 % (As)100 % (H)
Clipping factor on recovery0.97 (As)0.99 (Ca, 5-min data)1.00 (H)
Rain wash≥5 mm removes 90 % (I: 3.4 mm did nothing, 6.5 mm did)samesame
Energy E4,210,888 kWh measured meter (M)samesame
Tariff / cost₹7.75/kWh, ₹6/module × 4,840 = ₹29,040 per round (As)samesame

Tags: M measured · Ca calculated · I inferred · As assumed · H hypothetical. Loss, recoverable energy, rupees and interval are all calculated from these inputs.

4. Financial optimisation

Net = value of recovered energy − cleaning cost, against a rain-only baseline. B peaks broadly between ~22 and 35 days; below ~15 days every scenario except C loses money.

Net savings vs cleaning interval (real 2025–26 rain calendar).
Net savings vs cleaning interval (real 2025–26 rain calendar).
Scen.Best interval (simulated)T* = √(2C/pEr)Break-even cost per moduleWhole plant, one intervalBlock-specific intervals
Anone39 d₹3.2₹0₹0
B31 d26 d₹10.7₹90,987₹90,987
C16 d16 d₹29.4₹5,53,679₹5,54,859

Block-specific scheduling adds almost nothing: no block soils measurably faster, and kWh per module differs only 691–977 kWh/yr (Carport lowest).

Net savings (scenario B) vs tariff and cleaning cost, ₹/yr

Tariff \ cost per module₹3₹4₹5₹6₹8₹10₹12
₹5.0₹76,000₹56,000₹37,000₹17,000₹0₹0₹0
₹6.0₹1,04,000₹83,000₹64,000₹44,000₹6,000₹0₹0
₹7.0₹1,38,000₹1,10,000₹90,000₹71,000₹32,000₹0₹0
₹7.75₹1,64,000₹1,31,000₹1,10,000₹91,000₹52,000₹14,000₹0
₹8.0₹1,72,000₹1,39,000₹1,17,000₹98,000₹59,000₹20,000₹0
₹9.0₹2,07,000₹1,73,000₹1,44,000₹1,24,000₹86,000₹47,000₹8,000
₹10.0₹2,47,000₹2,07,000₹1,73,000₹1,51,000₹1,12,000₹74,000₹35,000

Like-for-like with the existing headline (incremental over an assumed current practice)

Scen.Current interval (assumed)ProposedExtra kWhExtra valueExtra costExtra net
A30 d61 d-8,379 kWh₹-64,934₹-1,45,200₹80,266
A45 d61 d-4,049 kWh₹-31,382₹-87,120₹55,738
A60 d61 d-284 kWh₹-2,203₹-29,040₹26,837
B30 d31 d-979 kWh₹-7,584₹-29,040₹21,456
B45 d31 d12,791 kWh₹99,127₹29,040₹70,087
B60 d31 d25,627 kWh₹1,98,607₹87,120₹1,11,487
C30 d16 d40,489 kWh₹3,13,791₹2,03,280₹1,10,511
C45 d16 d78,178 kWh₹6,05,878₹2,61,360₹3,44,518
C60 d16 d113,386 kWh₹8,78,738₹3,19,440₹5,59,298

The existing ₹3.65 L matches scenario C against a 45-day practice (₹3,44,518). It is an upper-bound number.

5. Sensitivity and uncertainty

The dust rate dominates everything; cleaning cost, rain threshold and tariff come next. Availability barely matters.

Tornado for scenario B (interval re-optimised for each bar except the interval bar).
Tornado for scenario B (interval re-optimised for each bar except the interval bar).
Variable (low / high)Net at lowNet at high
Soiling rate r (0.05 / 0.258 %/day)₹0₹5,16,873
Cleaning cost (Rs 12 / 3 per module)₹0₹1,69,744
Rain needed to wash (3 mm / 10 mm)₹32,474₹1,70,545
Electricity value (Rs 5 / 10 per kWh)₹17,498₹1,52,858
Dust saturates at 3 % (yes / no)₹0₹91,011
Interval fixed at 15 / 62 days (optimum 31)₹-57,552₹0
Share of dust a cleaning removes (80 % / 100 %)₹58,380₹1,01,881
Plant availability (95 % / 100 %)₹80,652₹91,011
Annual value, cost and net savings vs soiling rate, best interval each time.
Annual value, cost and net savings vs soiling rate, best interval each time.

Monte Carlo (1500 runs over the stated ranges: rate 0.04–0.26 %/d log-uniform, tariff ₹6–9, cost ₹4–10, removal 85–100 %, availability 96–100 %, clipping 0.97–1): median ₹0.69 L, P5 ₹0.00 L, P95 ₹3.70 L; 27 % of runs say routine cleaning does not pay. Bootstrap over rain events is not used (n = 2 informative events).

Distribution of net savings across assumption ranges.
Distribution of net savings across assumption ranges.

Bootstrap over the 113 detected intervals gives 0.258 %/d (95 % CI 0.214–0.313), but this only measures scatter of a biased estimator, so it is not used.

6. Physical and engineering validity

CheckPasses?Note
Energy within installed capacityMostly12 inverter-days and 1 plant-day exceed physical limits (logger dumps, max 9.99 kWh/kWp).
Temperature coefficientYes−0.29 %/°C (datasheet). The portal's '−0.0003' field is wrong.
Irradiance units consistentPartlyUnits fine (W/m², kWh/m²). Channel labelled POA is horizontal GHI; tilt not recorded.
No double-counting of soilingNo27 'cleanings' are recoveries from fault drops, counted as dust.
PR, PI, SR, efficiency kept apartPartlyPortal PR = yield ÷ GHI (not POA), so it hits 100–118 % on 3–10 Nov 2026. PI, SR and module efficiency are separate in this audit.
Cleaning cannot recover faults/downtimeFixed hereAudit uses measured meter energy (downtime already excluded) and a removal factor below 100 %.

7. Deliverables

7.1 Audit

See sections 1 and 6.

7.2 Corrected equations (only where a number changes)

Daily energy E: annual mean 11,537 kWh/d (measured), not a November forecast (~9,200 kWh/d).
T* = √(2C / (p·E·r)) = √(2 × 29,040 / (7.75 × 11,537 × 0.0010)) = 25 d (B; simulation with rain gives 31 d).
Daily soiling: s(d+1) = s(d) + r on dry days; rain ≥ 5 mm: s × 0.1; cleaning: s × (1 − η).
Recoverable energy = Σ E(d)·s_rain-only(d)·f_clip − Σ E(d)·s_with-cleaning(d)·f_clip = 72,391 kWh − 45,659 kWh = 26,732 kWh (B).
Net = 7.75 × 26,732 − 4 × 29,040 = ₹2,07,171 − ₹1,16,160 = ₹91,011 (B).
Rate evidence: r = rain jump ÷ dry days = 2.34 % ÷ 21 d = 0.11 %/d (B); 2.16 % ÷ 42 d = 0.05 %/d (A).

7.3–7.5 Scenario comparison, loss/savings table, graphs

Section 3 table; figures in sections 4–5.

7.6 Most influential assumptions

RankAssumptionSwing in B net
1Soiling rate r (0.05 / 0.258 %/day)₹5.17 L
2Cleaning cost (Rs 12 / 3 per module)₹1.70 L
3Rain needed to wash (3 mm / 10 mm)₹1.38 L
4Electricity value (Rs 5 / 10 per kWh)₹1.35 L
5Dust saturates at 3 % (yes / no)₹0.91 L

7.7 Data needed to validate scenario C

DataWhyHow
Crew cleaning log (date, block, modules, water, ₹)Replaces detected events; gives true interval and costFrom O&M team / Solar Ladder
Clean vs dirty reference pair on 2–3 roofs (one module cleaned daily)Direct soiling rate, incl. saturation60+ dry days, Oct–Jan and Mar–Jun
Pyranometer cleaning log + tilted reference cellRemoves sensor-dirt maskingClean sensor daily during test
String/MPPT current before and after a cleaningMeasured step per block5-min data, 3 days each side
Tilt, azimuth, string layout per blockCorrect transposition and shadingSite survey
Inverter alarm/event logSeparates faults from dustPortal has none; ask vendor
Actual cost per module and avoided tariffEconomicsCrew invoices, PSPCL bill

7.8 Recommendation for the presentation

Appendix

A1. Detector test (synthetic series are hypothetical, built from each block's real noise)

SeriesCleanings foundMedian stepMedian rate %/dr(step, days)Slope after cleaning %/d
Real data (Solpop events)1695.9 %0.2580.03-0.003
Real data (our re-run)2216.4 %0.3510.07–
No dust, noise only358.3 %0.4040.04-0.001
Linear dust 0.258 %/d + real cleanings1778.8 %0.4820.09-0.215

Reading: linear dust would leave a clear −0.2 %/day slope after each cleaning; the real data show none. The step-vs-gap correlation is near zero in every case, so it cannot decide between linear and saturating dust.

A2. Out-of-sample error of step models (on the 113 Solpop intervals, % points)

ModelScopeLeave-one-outLeave-one-block-out
constantblock1.66–
constantcampus1.831.84
constantseason1.801.83
linearblock5.30–
linearcampus3.893.91
linearseason3.883.89
linear+interceptblock2.07–
linear+interceptcampus1.841.85
linear+interceptseason1.821.85
saturatingblock2.11–
saturatingcampus1.992.01
saturatingseason1.992.02

Constant (1.83) ≈ linear+intercept (1.84) < saturating (1.99) < linear (3.89). A constant step wins because the steps are mostly threshold + noise, not because dust plateaus.

A3. Dry-window trends (clear days)

WindowReferenceDaysSlope %/d95 % CI
2025-12-01 to 2026-01-21pyranometer32+0.150+0.026 to +0.346
2025-12-01 to 2026-01-21ERA534-0.240-0.470 to -0.025
2026-01-25 to 2026-03-15pyranometer39+0.183+0.120 to +0.252
2026-01-25 to 2026-03-15ERA539-0.011-0.146 to +0.112
2026-03-20 to 2026-05-29pyranometer49+0.022-0.021 to +0.055
2026-03-20 to 2026-05-29ERA549+0.099+0.037 to +0.170
2026-10-12 to 2026-11-10pyranometer21+0.763+0.220 to +1.129
2026-10-12 to 2026-11-10ERA528-0.932-1.146 to -0.688

Slopes are dominated by the seasonal geometry curve and by smoke haze (ERA5, Oct–Nov), so they are not used as soiling rates.

A4. Method notes